HPH Series 20-120 kVA

Best-in-class power protection with maximum power and cost efficiency

Behind every great design there is an answer. Delta's true online double-conversion Ultron HPH Series is the solution for small and medium data centers and mission critical applications requiring highly reliable power protection and unbeatable energy efficiency.

The innovation behind the Ultron HPH Series UPS design incorporates low iTHD (<3%), 96% AC-AC and 99% ECO mode energy efficiency for increased Total Cost of Ownership (TCO) savings. Fully rated power (kVa=kW) without de-rating, the Ultron UPS offers leading AC-AC efficiency without sacrificing any available power requirements. Increased availability is further augmented through Ultron HPH watch-dog design.

Quite simply, the HPH Series UPS from Delta is a best-in-class (three phase 20/30/40/60/80/100/120 kVA UPS) power protection system that combines maximum available power, unsurpassed energy efficiency, and superior power performance with a significant advantage: TCO savings. HPH is an ideal choice for datacenters as well as for industries involved in factory equipment, communication systems, computer network systems, medical systems, monitoring systems and more. Since the Ultron HPH series UPS was launched in 2013, it has obtained wide adoption by customers and professional organizations worldwide, such as HPH 20kVA and 30kVA UPS for the luxury car manufacturers in Germany, key telecommunication operators in Asia, and international medical equipment providers in India, to name a few.

Swappable interior architecture for quick and easy maintenance; Redundant fan design enhances system reliability



お問い合わせはこちら

製品紹介

主な特長

Best-in-Class Power Performance and Efficiency

  • Fully rated power (kVA=kW) for maximum power availability
  • Leading AC-AC efficiency up to 96% saves energy costs
  • Low harmonic pollution (iTHD<3%) and high input power factor (>0.99) reduce upstream investment costs
 

Assured Reliability

  • Wide input voltage range allows the UPS to operate in harsh electrical environments and extends battery life
  • DSP based technology enables reduction in the number of electronic components to lower failure rate
  • Redundant auxiliary power and fan design* enhance system reliability
    (* Applied for models HPH-60/80/100/120K)
  • Watch-dog design of dual auxiliary power circuit to eliminate single-point failure to ensure reliability
  • Built-in manual bypass ensures continuous power to the load even if the UPS is under maintenance
 

Greater Flexibility

  • A wide choice of configurations, such as N+X redundancy and hot stand-by
  • Adjustable charging current and charging voltage meet different battery configuration requirements
  • Flexible battery configuration optimizes battery investment
 

Superior Serviceability and Management

  • Front-door battery replacement with hot-swappable battery tray design supports easy and quick replacement without turning the unit off (HPH-B / BN)
    HPH-B: UPS integrated battery model has batteries inside
    HPH-BN: UPS integrated battery model has no batteries inside
  • Swappable interior architecture and front access servicing enables quick and easy maintenance
    (Applied for models HPH-60/80/100/120K)
  • Multi-connectivity interface supports remote UPS monitoring and management
アプリケーション

仕様
  1. Model
  2. HPH-20K, HPH-30K, HPH-40K,
    HPH-60K, HPH-80K, HPH-100K, HPH-120K
    HPH-20K-BN/B, HPH-30K-BN/B, HPH-40K-BN/B

  3. Power Rating
  4. HPH-20K : 20kVA / 20kW
    HPH-30K : 30kVA / 30kW
    HPH-40K : 40kVA / 40kW
    HPH-60K : 60kVA / 60kW
    HPH-80K : 80kVA / 80kW
    HPH-100K : 100kVA / 100kW
    HPH-120K : 120kVA / 120kW

  5. Input
  6. Nominal Voltage : 380/220Vac, 400/230Vac, 415/240Vac (3 phase, 4-wire + G)
  7. Voltage Range
    HPH-20K/30K/40K: 300~477Vac (full load), 228~300Vac (70~100% load)
    HPH-60K/80K/100K/120K: 332~477Vac (full load), 228~332Vac (63~100% load)
  8. Frequency: 40~70Hz
  9. Power Factor: > 0.99 (full load)
  10. Current Harmonic Distortion: < 3%

  11. Output
  12. Voltage: 380/220Vac, 400/230Vac, 415/240Vac (3 phase, 4-wire + G)
  13. Voltage Regulation: ±1%
  14. Voltage Harmonic Distortion
    HPH-20K/30K/40K: < 1.5% (linear load)
    HPH-60K/80K/100K/120K: < 2% (linear load)
  15. Overload Capability
    ≤ 105%: continuous
    106~≤ 125%: 10 minutes
    126~≤ 150%: 1 minute
    > 150%: 1 second
  16. Output Power Factor: 1
    Frequency: 50/60Hz ± 0.05Hz

  17. Battery
  18. Battery Voltage: 240Vdc
  19. Type: Support SMF/VRLA/Tubular/Ni-Cd
  20. Quantity
    HPH-20K/30K/40K: 32~50pcs
    HPH-60K/80K/100K/120K: 32~46pcs***
  21. Charge Current (Max.) Built-in
    HPH-20K: 5A
    HPH-30K/40K: 9A
    HPH-60K: 10A
    HPH-80K: 15A
    HPH-100K/120K: 20A
  22. Typical Backup Time**
    HPH-20K-BN/B: 15min
    HPH-30K-BN/B: 10min
    HPH-40K-BN/B: 9.5min

  23. Communication Interfaces
    SMART Slot x 1, MINI Slot x 1, Parallel Port x 2, RS232 Port x 1, REPO Port x 1, Charger Detection Port x 1, Input Dry Contact x 2, Output Dry Contact x 6, USB Port x 1*

  24. Conformance
  25. Safety: CE, RCM
  26. UPS Classification According to IEC 62040-3: VFI-SS-111

  27. Other Features
  28. Parallel Redundancy: Up to 4 units
  29. Emergency Power Off: Yes (local and remote)
  30. Maintenance Bypass Switch: Yes

  31. Efficiency
  32. AC-AC
    HPH-20K/30K/40K: Up to 96%
    HPH-60K/80K/100K/120: > 96% (HPH 40-120kVA efficiency is tested by TÜV)
  33. ECO Mode: Up to 99%

  34. Environment
  35. Operating Temperature: 0~40˚C
  36. Relative Humidity: 5~ 95% (non-condensing)
  37. Audible Noise
    HPH-20K: < 55dB
    HPH-30K/40K: < 60dB
    HPH-60K/80K/100K/120K: < 65dB

  38. Physical
  39. Dimensions (W x D x H)
    HPH-20K/30K/40K: 380 x 800 x 800mm
    HPH-60/80K: 520 x 800 x 1175mm
    HPH-100/120K: 520 x 800 x 1760mm
  40. Weight
    HPH-20K: 66.5kg
    HPH-30K: 86.06kg
    HPH-40K: 86.5kg
    HPH-60K: 186.5kg
    HPH-80K: 191kg
    HPH-100K/120K: 312kg

  41. Physical (BN/B)
  42. Dimensions (W x D x H)
    HPH-20K/30K/40K: 490 x 830 x 1400mm
  43. Weight (with batt.)
    HPH-20K-B: 365kg
    HPH-30K-B/40K-B : 385kg
  44. Weight (without batt.)
    HPH-20K-BN: 131kg
    HPH-30K-BN/40K-BN : 162kg

  45. HPH-B: UPS integrated battery model has batteries inside
    HPH-BN: UPS integrated battery model has no batteries inside

    * Applied for models HPH-60K/80K/100K/120K
    ** At 70% load with internal battery strings.
    *** UPS needs de-rating for battery quantity 32~36pcs. Please contact authorized Delta personnel.

    All specifications are subject to change without prior notice.
ダウンロード

HPH Series 20/30/40/60/80/100/120 kW UPS (Leaflet) / 208KB
for EMEA, SEA, South America, Korea (English)

 

HPH Series 20/30/40/60/80/100/120 kW UPS (Leaflet) / 429KB
for China (Simplified Chinese)

 

HPH Series 20/30/40 kW UPS (Leaflet) / 668KB
for Taiwan (Traditional Chinese)

 

HPH Series 20/30/40/60 kW UPS 208/120V (Leaflet) / 962KB
for North and South America (English)

 

HPH Series 20/30/40 kW UPS (User Manual) / 4.40MB

 

HPH Series 20/30/40 kW UPS - integrated battery model (User Manual) / 4.52MB

 

HPH Series 60/80/100/120 kW UPS (User Manual) / 2.56MB

 


お問い合わせはこちら